CHINA
Hall C3
C3-7631
Valves and Actuators, Instrumentation
Input signal: 4 ~ 20mA current or digital signal
Input impedance: 540Ω
Basic error: ±0.5%
Hysteresis error: ≤0.5%
Dead zone: 0.1% (minimum)
Air supply pressure: 0.2 ~ 0.6MPa
Airconsumption: ≤0.6NL/min
Stroke: 10 ~ 100mm (Angle 50 ~ 90°)
Ambient temperature: -40 ~ +80°C
Display device: LCD
Explosion-proof : Ex ia II C T4 · · T6 Gb, Ex ia III C T85℃ · · · T135℃ Db
Ex db IIB/IIC T4 · · · T6 Gb, Ex tb IIIC T85℃ · · · T135℃ Db
Ingress Protection : IP66
Lightning protection: peak voltage 12.0kV, peak current 1.0kA
Shell material: Aluminum alloy/stainless steel