OMICRON CPC 100 – All-in-One Primary Test System
Overview
The CPC 100 is a multi-functional test device designed for primary testing of substation components. It replaces multiple single-function devices and supports a wide range of tests for commissioning, diagnostics, and maintenance.
Key Capabilities
High Output Power:
Up to 800 A AC, 400 A DC, or 2 kV AC (expandable to 2 kA / 12–15 kV with accessories)Frequency Range:
15 Hz to 400 Hz variable outputPower Output:
Up to 5 kVACompact & Portable:
Weighs 29 kg, runs from a single-phase wall outlet
Supported Test Applications
Current Transformers (CTs)
Ratio, burden, excitation, knee point, demagnetization, ALF, withstand voltage, Rogowski/LPCTVoltage Transformers (VTs)
Ratio, polarity, burden, insulation testingPower Transformers
Winding resistance, excitation current, turns ratio, OLTC test, insulation condition (PF/DF), leakage reactance, demagnetizationCables & Lines
Line impedance, k-factor, mutual couplingGrounding Systems
Ground grid impedance, step & touch voltage, soil resistivityRotating Machines
PF/DF test, tip-up test, DC resistance, pole drop, stray flux, stator core testGIS & Switchgear
HV withstand, insulation test, contact resistance, partial discharge (with accessories)Protection System Commissioning
End-to-end test from CT/VT → relay → circuit breakerIEC 61850 Sampled Values Testing
Closed-loop test via Merging Units (MUs)
Software & Operation
Primary Test Manager™ (PTM):
Asset-based testing, data management, automatic reporting, wiring diagramsPTMate App:
Mobile assistant for quick data entry, safety checks, and test controlFront Panel Operation:
Quick tests via test cards or custom templates
Safety Features
Emergency stop button
Grounding check
Overload protection
Discharge circuits
Safety key lock
Expandable with Accessories
CP CB2: Current booster (up to 2,000 A)
CP TD12/15: PF/DF measurement (up to 15 kV)
CP SB1: Switch box for OLTC testing
CP CU1: Line/cable coupling unit
CP RC: GIS resonance testing
CPOL2: Polarity checker
HGT1: Handheld grounding tester
Technical Highlights
Spec | Value |
---|---|
Max Current | 800 A AC / 400 A DC (2 kA with booster) |
Max Voltage | 2 kV AC (12–15 kV with booster) |
Power Output | Up to 5 kVA |
Accuracy | Typical <0.05% amplitude, <0.10° phase |
Weight | 29 kg |
Interfaces | USB, Ethernet, Binary I/O |
Frequency Range | 15–400 Hz |